Tinjauan produk
Rincian produk
Ngundeur Data
Produk patali
Kontak Kami
1. Overload panyalindungan
2. Perlindungan sirkuit pondok
3. Ngadalikeun
4. Dipaké dina wangunan padumukan, wangunan non-padumukan, industri sumber énergi jeung infrastruktur
5. Numutkeun jinis pelepasan sakedapan digolongkeun kieu: tipe B(3-5)ln, tipe C(5-10)ln, tipe D(10-20)ln
Tipe | Uji ayeuna | Waktos tripping | Hasil anu dipiharep | Tipe | Uji ayeuna | Waktos tripping | Hasil anu dipiharep | |
B, C, D | 1.13 Dina | t≤1h(Dina≤63A) | Teu tripping | B | 3 Dina | t≤0.1s | Teu tripping | |
1.13 Dina | t≤2h(Dina>63A) | C | 5Di | t≤0.1s | ||||
B, C, D | 1,45 di | t<1h(Dina≤63A) | Ngajanteng | D | 10 Dina | t≤0.1s | ||
1,45 di | t<2h(Di>63A) | B | 5Di | t <0.1s | Ngajanteng | |||
B, C, D | 2,55 di | 1s | Ngajanteng | C | 10 Dina | t <0.1s | ||
2,55 di | 1s32A) | D | 20 Dina | t <0.1s |
Tipe | Standar | lEC/EN 60898-1 | |
Fitur listrik | Dipeunteun ayeuna ln | A | 1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63 |
Kutub | P | 1, 2, 3, 4 | |
tegangan dipeunteun Ue | V | 230/400 | |
tegangan insulasi Ui | V | 500 | |
Frékuénsi dipeunteun | Hz | 50/60 | |
Kapasitas pegatna dipeunteun | A | 4500 | |
Dipeunteun dorongan tahan tegangan (1.2/50)Uimp | V | 4000 | |
Tegangan uji diéléktrik dina ind.Frek.keur 1 mnt | kV | 2 | |
Gelar polusi | 2 | ||
Ciri pelepasan termo-magnétik | B, C, D | ||
Fitur mékanis | Kahirupan listrik | t | 6000 |
Kahirupan mékanis | t | 20000 | |
Gelar panyalindungan | IP20 | ||
Suhu rujukan pikeun netepkeun unsur termal | ℃ | 30 | |
Suhu lingkungan (kalayan rata-rata poean≤35 ℃) | ℃ | -5~+40 | |
Suhu neundeun | ℃ | -25~+70 | |
Pamasangan | Jenis sambungan terminal | kabel / Pin-tipe busbar | |
Ukuran terminal luhur / handap pikeun kabel | mm² | 25 | |
AWG | 3月18 | ||
Ukuran terminal luhur / handap pikeun busbar | mm² | 25 | |
AWG | 3月18 | ||
Torsi tightening | N*m | 2 | |
Dina-Ibs | 18 | ||
Pamasangan | Dina rel DIN EN 60715 (35mm) ku alat klip gancang | ||
Sambungan | Ti luhur atawa handap |